Collection: Fireye Flame-Monitor System (E-Series Flame Safeguards)

Fireye Flame Monitor system (also referred to as Flame-Monitor or E-Series) is one of the most reliable, versatile, and well-known flame safeguard systems available on the market. This modular microprocessor-based system offers two flame safeguard controls: E110 for 120 VAC (+10%, -15%) 50/60 Hz, and E120 for 220 VAC (+10%, -15%) 50/60 Hz. The exact functionality of Flame-Monitor depends on a chosen programmer, amplifier, scanner, chassis, and wiring base.

When combined with limit and operating controls, the Flame-Monitor system manages the burner/blower motor, ignition system, and fuel valves to ensure safe and reliable burner operation for oil, gas, and combination fuel burners.

While both E110 and E120 controls have a display that shows current operating status and lockout information in the event of a safety shutdown, there is also a remote display option and expansion modules (E300 and E320) that provide additional operational information, such as identification of the specific limit in the operating control circuit or running interlock circuit that caused the burner shutdown or lockout. The display and expansion module reduce troubleshooting time and expense. 

Multiple Flame Monitor units can be connected together in a serial chain (daisy-chain) via Modbus RTU using RS-485 under the condition that the units use the same baud rate. Modbus RTU is available from the EP/EPD programmer using connection board ED610 with an ED512 cable. Modbus allows access to all current operating information from the base and expanded annunciator, as well as complete lockout history. 

Main Features of Fireye Flame Monitor system:

  • Non-volatile memory keeps a history of events and the present position in case of power outage.
  • Display shows readouts of a constant flame signal and main fuel operational hours and complete cycles.
  • Selectable purge time via DIP switches located on the EP programmer.
  • A run/check switch that allows the operator to stop the program sequence.
  • Modbus communications via RS485 multi-drop link.

 

Flame Monitor Amplifiers and Scanners:

E1R1, E1R2, and E1R3 are autocheck infrared amplifiers with different profiles. All these amplifiers utilize 48PT2 IR scanners. Fireye recommends E1R1 for general-purpose use except solid fuel applications (E1R1 is engineered for oil fog rejection).

ERT1 is a rectification amplifier designed to work with a 69ND1 flame rod.

EUV1 is a standard ultraviolet amplifier engineered for UV1A or UV90 UV scanners.

EUVS4 is a self-checking ultraviolet amplifier that requires a 45UV5 UV scanner.

 

Legacy and Obsolete Management

Legacy EPD programmers can be replaced with the current EP programmers for the required operational sequence. Fireye recommends to match the numbers at the end of part numbers, but some models require additional configurating via a DIP switch, jumpers, or alternative wiring arrangements. Also, to achieve the full functionality when using an EP programmer to replace an EPD, Fireye recommends adding the ED510 display. Without a display, an external reset button must be connected to reset lockouts.